§ 7-84. Fire pumps.  


Latest version.
  • Fire pumps shall serve only the building or structure for which they were installed and shall not be shared with other buildings or structures, except that a single fire pump may be shared between a building and up to 2 parking structures if all of the following are provided:

    (a)

    All buildings and structures are under the same ownership.

    (b)

    A "unity of title" for the buildings and structures is provided before the installation permit is issued.

    (c)

    The fire mains serving each building/structure are installed underground in accordance with NFPA 24, and this article.

(Ord. No. 5430, § 2, 12-12-17)